The online version is open to any electronic equipment, at the same time, the online version of our CDCS study materials can also be used in an offline state. You just need to use the online version at the first time when you are in an online state; you can have the right to use the version of our CDCS Study Materials offline. And if you are willing to take our CDCS study materials into more consideration, it must be very easy for you to pass your CDCS exam in a short time.
EXIN CDCS Exam Syllabus Topics:
Topic | Details |
---|---|
Topic 1 |
|
Topic 2 |
|
Topic 3 |
|
>> Pass4sure CDCS Dumps Pdf <<
Exam CDCS Quiz - CDCS Exam Reference
The trouble can test a person's character. A bad situation can show special integrity. When to face of a difficult time, only the bravest people could take it easy. Are you a brave person? If you did not do the best preparation for your IT certification exam, can you take it easy? Yes, of course. Because you have LatestCram's EXIN CDCS Exam Training materials. As long as you have it, any examination do not will knock you down.
EXIN EPI Certified Data Centre Specialist Sample Questions (Q35-Q40):
NEW QUESTION # 35
A computer room with a raised floor has been designed with racks in a hot/cold aisle setup.
What should you recommend for the placement of down-flow air conditioners?
- A. Air conditioners perpendicular to (at the end of the row of) the Hot-Aisle
- B. Air conditioners perpendicular to (at the end of the row of) the Cold-Aisle
- C. Air conditioner placement has no influence on cooling effectiveness and efficiency. Hence, they can be placed at any convenient location.
- D. Air conditioners should always be placed at both sides of each row of racks
Answer: B
Explanation:
In a hot/cold aisle configuration, placing down-flow air conditioners perpendicular to the cold aisle ensures that cool air is directed efficiently into the cold aisles where server intakes are located. This layout allows for optimal cooling performance by aligning the airflow directly with the equipment intakes, minimizing hot spots and enhancing cooling efficiency.
Detailed Explanation:
With a raised floor design, cold air from the air conditioners is supplied into the cold aisle, where server intakes are located. Positioning the air conditioning units perpendicular to the cold aisles ensures that cool air is delivered directly into these aisles, preventing air mixing and optimizing cooling. This setup takes full advantage of the airflow management strategy inherent to the hot/cold aisle configuration.
EPI Data Center Specialist References:
EPI guidelines on cooling emphasize that down-flow air conditioners should be positioned to maximize the effectiveness of cold aisle delivery, which improves cooling efficiency and helps maintain consistent temperatures across server racks.
NEW QUESTION # 36
When shielding material reaches its saturation point, what will be the impact?
- A. The shielding material will reach its maximum electrically charged state.
- B. The shielding material will no longer be able to attenuate (reduce) additional EMF.
- C. The shielding material will increase its permeability factor.
- D. The shielding material will reach its optimal shielding performance state.
Answer: B
Explanation:
When shielding material reaches its saturation point, it can no longer effectively attenuate additional EMF. At saturation, the material's ability to absorb or redirect magnetic fields is exhausted, meaning it cannot provide further shielding beyond this point. Additional EMF exposure would pass through the material without significant reduction.
Detailed Explanation:
Saturation occurs when the material's magnetic domains are fully aligned with the magnetic field, leaving no capacity to absorb or deflect further EMF. This can happen with high EMF levels, beyond the material's design limits, resulting in a breakdown of shielding effectiveness.
EPI Data Center Specialist References:
EPI guidelines on EMF management indicate that selecting appropriate shielding materials with sufficient capacity is essential to prevent saturation and ensure continuous protection. Saturation limits should be considered during design to avoid compromised shielding performance.
NEW QUESTION # 37
A new network storage device in a non-standard size rack of approximately 600 kg/1,300 lbs is going to be installed in the data center.
Are new floor loading calculations required?
- A. Yes, a structural engineer, approved/endorsed by the building owner, should carry out new floor loading calculations.
- B. Yes, additional floor loading calculations need to be done by the floor manager, which should be verified by the safety engineer.
- C. No, as long as the equipment is less than 700 kg/1,500 lbs it will be within the limits.
- D. No, specifications of equipment brought into the data center will already be known during the design of the data center, and therefore the floor will be able to handle it.
Answer: A
Explanation:
For heavy equipment, such as a network storage device weighing approximately 600 kg/1,300 lbs, new floor loading calculations are indeed required, particularly since the rack is non-standard. A structural engineer, approved by the building owner, should conduct these calculations to ensure the floor can safely support the new load without risking structural integrity.
Detailed Explanation:
Data centers are designed with specific floor load ratings, which are determined during the design phase based on anticipated equipment. When adding or replacing equipment that is significantly heavy or non-standard, reassessing the floor's capacity is essential to avoid overloading. A structural engineer has the expertise to verify if the existing floor can accommodate the weight and, if not, can recommend reinforcement measures.
This step ensures compliance with safety standards and helps prevent damage to the infrastructure, which could lead to costly repairs or even catastrophic failure in extreme cases.
EPI Data Center Specialist References:
EPI Data Center Specialist training advises that any changes in the data center load, particularly involving non-standard and heavy equipment, warrant a structural assessment. Ensuring compliance with floor load capacity is a critical safety and operational concern, as underscoring data center infrastructure reliability and safety is a priority in EPI's best practices.
NEW QUESTION # 38
Management has requested a 15-minute battery bank assuming full load on the UPS. The UPS vendor has provided the following specifications of the UPS:
* Rated power: 30 kVA
* Rectifier input voltage: 400 V/3 phase
* Rectifier input power factor: 0.8
* Battery rated voltage: 384 V
* Number of cells: 192
* End of discharge voltage: 308 V
* Inverter output voltage: 400 V/3 phase
* Inverter output power factor: 0.8
What information is missing to perform the battery calculation?
- A. UPS efficiency
- B. Load imbalance on the phases
- C. Available battery charging current
- D. Inverter efficiency
Answer: A
Explanation:
To determine the required capacity of the battery bank for the 15-minute runtime at full load, one must know the total power requirement that the battery bank must supply. The specifications provided include most of the necessary details, such as rated power, input voltage, battery voltage, and discharge voltage. However, one critical piece of information is missing: the UPS efficiency.
Detailed Explanation:
In a data center UPS system, the battery bank is designed to supply power for a set duration when there is an input power failure. The UPS efficiency affects the actual power the UPS can deliver to the load compared to the power it draws from the batteries. The efficiency factor is necessary to accurately calculate the required capacity of the battery bank since it determines how much input power is needed from the batteries to supply the load at full capacity. The formula typically used to determine battery capacity involves factoring in UPS efficiency, as it allows you to understand the losses within the UPS system.
If UPS efficiency is not considered, there would be an inaccurate estimation of the actual power needed from the batteries. For instance, if a UPS has 90% efficiency, only 90% of the power drawn from the batteries reaches the load. Without knowing this efficiency, it is not possible to calculate the battery bank size accurately, as you cannot accurately estimate the losses within the UPS itself.
EPI Data Center Specialist References:
According to EPI Data Center Specialist training, understanding the UPS efficiency is essential for battery sizing. Without it, the calculations could lead to either undersizing or oversizing the battery bank, which affects both reliability and cost-effectiveness of the UPS system. The EPI Data Center Specialist course emphasizes that battery sizing must account for all losses within the UPS system, with efficiency being a primary factor in these calculations.
NEW QUESTION # 39
What should you consider when using raised floor tiles with air deflectors or louvers?
- A. Tiles with air deflectors or louvers will reduce the cooling capacity of the tile.
- B. Tiles with air deflectors or louvers can be very heavy.
- C. Tiles with air deflectors or louvers do not allow for a flexible cooling solution.
- D. Tiles with air deflectors or louvers can only be used to cool storage equipment.
Answer: B
Explanation:
Raised floor tiles with air deflectors or louvers are typically heavier than standard tiles due to the additional materials and mechanisms used to direct airflow. The added weight can pose challenges for installation and adjustment, and consideration must be given to the floor's load capacity and ease of maintenance.
Detailed Explanation:
Tiles with deflectors or louvers help direct airflow, enhancing cooling efficiency by focusing cool air where needed. However, these tiles are often heavier, which can affect handling and require reinforced raised floor systems. It's essential to factor in the weight for any floor tile replacements or installations to ensure they are compatible with the raised floor's structural capacity.
EPI Data Center Specialist References:
EPI data center design training mentions the potential impact of heavy tiles on floor handling and load capacity. Data center operators need to plan for safe handling and load-bearing capacity when using such specialized tiles.
NEW QUESTION # 40
......
With our CDCS study materials, only should you take about 20 - 30 hours to preparation can you attend the exam. The rest of the time you can do anything you want to do to, which can fully reduce your review pressure. Saving time and improving efficiency is the consistent purpose of our CDCS Learning Materials. With the help of our CDCS exam questions, your review process will no longer be full of pressure and anxiety.
Exam CDCS Quiz: https://www.latestcram.com/CDCS-exam-cram-questions.html
- Testing CDCS Center ???? Latest CDCS Study Materials ???? Reliable CDCS Exam Blueprint ???? Simply search for ➠ CDCS ???? for free download on 「 www.lead1pass.com 」 ????Test CDCS Questions Answers
- CDCS Valid Test Papers ???? Test CDCS Preparation ???? CDCS Certification Exam Cost ???? Search for [ CDCS ] and easily obtain a free download on ➽ www.pdfvce.com ???? ????Latest CDCS Study Materials
- Quiz 2024 EXIN Accurate Pass4sure CDCS Dumps Pdf ???? Search for ➤ CDCS ⮘ and obtain a free download on “ www.examcollectionpass.com ” ????CDCS PDF
- Free PDF EXIN - CDCS - Professional Pass4sure EXIN EPI Certified Data Centre Specialist Dumps Pdf ???? Simply search for { CDCS } for free download on ➡ www.pdfvce.com ️⬅️ ????Pass CDCS Guide
- EXIN CDCS Questions: Turn Your Exam Fear into Confidence [2024] ???? Simply search for ➠ CDCS ???? for free download on ➠ www.itcerttest.com ???? ????CDCS PDF
- Pass CDCS Guide ???? Latest CDCS Demo ???? New CDCS Test Camp ???? Download ➥ CDCS ???? for free by simply searching on ⏩ www.pdfvce.com ⏪ ????CDCS Visual Cert Exam
- CDCS Valid Exam Voucher ???? CDCS Visual Cert Exam ???? CDCS Latest Exam Labs ???? Go to website ⮆ www.pass4leader.com ⮄ open and search for ⮆ CDCS ⮄ to download for free ????Latest CDCS Study Materials
- Unparalleled EXIN Pass4sure CDCS Dumps Pdf Are Leading Materials - Trustworthy CDCS: EXIN EPI Certified Data Centre Specialist ???? Search on ✔ www.pdfvce.com ️✔️ for ✔ CDCS ️✔️ to obtain exam materials for free download ????CDCS Related Content
- Test CDCS Questions Answers ???? CDCS Reliable Dumps Sheet ???? Latest CDCS Exam Labs ???? Go to website ▛ www.torrentvalid.com ▟ open and search for 【 CDCS 】 to download for free ????New CDCS Test Camp
- 100% Pass EXIN - CDCS - EXIN EPI Certified Data Centre Specialist –Efficient Pass4sure Dumps Pdf ???? Go to website 《 www.pdfvce.com 》 open and search for { CDCS } to download for free ????CDCS PDF
- CDCS Visual Cert Exam ???? CDCS Related Content ???? Exam Topics CDCS Pdf ???? Search for ▶ CDCS ◀ on ⏩ www.examsreviews.com ⏪ immediately to obtain a free download ????Test CDCS Result
- CDCS Exam Questions